AXQ / TXXI 1kV 1x150mm²A

Description

Description

Standards

  • International
    EN 50267-2-1; EN 50267-2-2; EN 50268-2; IEC 60228; IEC 60754-1; IEC 60754-2; IEC 61034

AXQ/TXXI (S1XZ1-AR) is a halogen free, XLPE-insulted and HFFR sheathed cable with circular, stranded aluminum conductor. The cable is designed according to SS 424 14 18. The conductors have resistance according to IEC 60228 class 2. The sheath is marked "NEXANS GS AREA mm2 1kV Ds2d2a2 year+month". AXQ/TXXI meets the requirements for flame class Dcas2d2a2 according to CPR.

 

Lifemark(TM) recycling marking

The external surface of the outer sheath is embossed with a text which specifies all components in the polymers and prepares the cable for future recycling.

 

Quality system

Designed, manufactured and tested in accordance with ISO 9001.

 

Environmental management system

The activities at our plant in Grimsås are certified according to ISO 14001.

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Aluminum
Type of conductor
Circular, stranded, class 2
Insulation
XLPE
Outer sheath
HFFR (polyolefin)
Lead free
Yes
Conductor flexibility
Class 2
Conductor shape
Circular
Halogen free
Yes
With Green/Yellow core
No
With smaller neutral conductor
No

Dimensional characteristics

Dimensional characteristics

Conductor cross-section
150 mm²
Number of cores
1
Conductor diameter
14.1 mm
Nominal insulation thickness
1.4 mm
Diameter over insulation
16.9 mm
Nominal outer sheath thickness
1.6 mm
Nominal outer diameter
20.1 mm
Approximate weight
580 kg/km
Neutral conductor section (when smaller)
- mm²

Electrical characteristics

Electrical characteristics

Max. DC resistance of the conductor at 20°C
0.206 Ohm/km
Operating Voltage Vo DC
1500 V
Perm. current rating buried 15°C - flat formation
395 A
Perm. current rating buried 15°C - trefoil formation
360 A
Perm. current rating in air 25°C - flat formation
425 A
Perm. current rating in air 25°C - trefoil formation
375 A
Permissible short circuit current
13500 A
Rated Voltage Uo/U (Um)
0,6/1 kV

Mechanical characteristics

Mechanical characteristics

Maximum pulling force by laying
4.5 kN

Usage characteristics

Usage characteristics

Minimum operating temperature
-40 °C
Ambient installation temperature, range
-10 ... 50 °C
Bending factor when laying
10 (xD)
Maximum operating temperature
90 °C
U.V resistance
Very good

Resources

Resources

Selling & delivery Information

AXQ/TXXI will be delivered in lengths of 500 m. The drum is marked with manufacturer, type of cable and length. The ends of the cable are sealed.

Declaration of Performance

  • Declaration of Performance n� : 1000919-SEGR
  • Certification Date : 1/8/20
  • AVCP (Assessment and Verification of Constancy of Performance) : System 3
  • Notified body : 0366
  • Declared performance : Dca-s2,d2,a2

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close