AXQJ TT 24 kV 3-core (CPR)

Description
The cable may be used for fixed installation indoors and outdoors in air, ground and water.

Description
Standards
International : HD 620 S2 2010 10M; IEC 60754-1; IEC 60754-2; IEC 61034-1/2National : SS 424 14 16
Description
AXQJ TT is a longitudinally and radially waterblocked, XLPE-insulated, CCA screened (aluminium wire with a corrosion protective layer of copper) and HFFR sheated 3-core cable with circular aluminium conductors.. The concentric screen and the aluminium foil has longitudinal contact. The cable is designed in applicable parts according to HD 620 S2 10M. The conductors are longitudinally water blocked have resistance and number of wires according to IEC 60228 class 2. The sheath is marked type/manufacturer/year+month/metre marking. AXQJ TT meets the requirements for fire class Dcas2d2a2 according to CPR.
Standards
The cable can be loaded according to SS 424 14 16.
Quality and environmental management system
Certified according to ISO 9001, IRIS, ISO/TS 16949 and ISO 14001.
Characteristics
Construction characteristics | |
---|---|
Conductor material | Aluminum |
Conductor shape | Round, stranded |
Insulation | XLPE (chemical) |
Outer sheath | HFFR (Halogene Free Flame Retardant) |
Colour | Black |
Lead free | Yes |
Dimensional characteristics | |
Number of cores | 3 |
Electrical characteristics | |
Operating voltage | 24kV |
Usage characteristics | |
Minimum installation temperature | -10°C |
Recommended minimum installation temperature | 0°C |
Maximum operating temperature | 90°C |
Short-circuit max. conductor temperature | 250°C |