Dansk Login Get Registered Catalog Browser Contact Us
Global expert in cables and cabling system

About Nexans

Products and Solutions

Customer Service

Work at Nexans

News and Press

Go

LANmark-OF MPO-MPO Slim Pre-Term for Singlemode (OS2), OM3 and OM4

Send link to this page print Your Nexans contact on this page
LANmark-OF MPO-MPO Slim Pre-Term for Singlemode (OS2), OM3 and OM4
  • Factory terminated MPO-MPO fibre assembly
  • Easy installation of Pre-Term since assembly can bend in any direction.
  • Small diameter of cable to reduce data centre space
  • Polarity in optical channel is easily maintained by its advanced design
  • Only one type of patch cords and one type of cassettes required
  • 12 fibres
  • Fibre type: Singlemode (OS2), OM3 and OM4
  • Normal and low loss connectivity
LANmark-OF
Description

 

MPO-MPO Pre-Term characteristics

The round cable design facilitates the installation of the MPO-MPO Pre-Term: the small bending radius of only 30 mm in any direction eliminates the problems of preferential bending associated with traditional ribbon MPO cables.

Polarity in the optical channel during installation is guaranteed due to a pair flip fibre construction.  This is in agreement with standard TIA 568-B-1-7-2006 method C. It allows the continuous use of the standard patch cords eliminating the need to buy optically straight patch cords. Also polarity is maintained with the same type of cassette on both sides of the channel without the need to flip the cassette on one side.

The Pre-Term is available with OM3, OM4 and singlemode fibres.  The singlemode fibres are according to the specifications for G652D and OS2 cables.  Details on the fibre specifications can be found in the detailed fibre datasheets.

The typical value for the insertion loss for a normal loss MPO-MPO connection is 0,3 dB. The limit value is 0,6 dB measured according to standard IEC61300-3-45.


The typical value for the insertion loss for a low loss MPO-MPO connection is 0,2 dB. The limit value is 0,35 dB measured according to standard IEC61300-3-45.
 

Mechanical characteristics of the Pre-Term are conform to the IEC-60794-20 standard for indoor cables.

The small diameter of 2.5 mm of the cable reduces significantly the expensive space required for cabling in a data centre and facilitates the airflow.

The MPO-MPO Pre-Term has standard non-pinned (female) connectors. This matches with the pinned (male) connectors in the MPO modules.

 

Consistent quality

In order to produce high quality, reliable pre-terminated multi-fibre cables, there are a number of physical characteristics that must be addressed. Therefore, all LANmark-OF MPO-MPO Pre-Term are fully terminated and tested in a quality assured factory environment.   They are delivered with these test results. 

 

 

MPO-MPO Pre-Term Benefits

 

  • Short & reliable manufacturing lead-time
  • Fast installation times
  • No specialised termination training required
  • No consumables, termination tool kits
  • No cable preparation necessary
  • No cable or connector scrap
  • No termination errors on site
  • Delivered fully tested, labelled and documented
  • Improved end-to-end attenuation
  • Reduced on-site disruption and installation time
  • Cost effective solution

 TOP
Characteristics
Dimensional characteristics
Approximate weight 5.5kg/km  
Outer Diameter 2.5mm  
Mechanical characteristics
Maximum pulling force (IEC 60794-1-2-E1) 400N  
Crush resistance (IEC 60794-1-E3) 50N/cm  
Usage characteristics
Operating temperature, range 0 .. 50°C  
Storage temperature, range -40 .. 60°C  
Fire retardant IEC 60332-3  
Flame retardant IEC 60332-1  
Minimum static operating bending radius 30mm  

 TOP
Insertion loss for individual MPO connection

Fibre type

Multimode (OM3 or OM4)

Singlemode (OS2 with G652D)

Normal loss connection -Typical loss

0.3 dB

0.3 dB

Normal loss connection - Max loss

0.6 dB

0.6 dB

Low loss connection - Typical loss

0.15 dB

0.15 dB

Low loss connection - Max loss

0.3 dB

0.3 dB

Measured in manufacturing according to standard IEC 61300-3-45

N-number codification: N15A.P12QVXXX

Letter in N-number

Description

Variations

A

Fibre type

4: SM (OS2) or 5: OM3, 7: OM4

Q

Performance

Normal (S) or low loss (L)

V

Fanout type

Default (N): No pulling eye and protection tube

XXX

Length between glands

001-300 m

Example: N155.P12LN050: LANmark-OF MPO-MPO Slim Pre-Term with 12 OM3 fibres, low loss connectors with a length of 50 m between the cable glands.

 TOP