WINDLINK® H07 ZZ-F 90°C

New
Send link to this page print Your Nexans contact on this page
WINDLINK® H07 ZZ-F  90°C

CENELEC HD 22-13; EN draft 50525.2
CENELEC HD 22-12 (for high temperature 90°C continuous service - ageing test performance)

Standards
International  CENELEC HD22-13
Description

Application

This cable is specially designed for Wind Turbines and to be used for the Loop .
It can be used up to 1000V in case of fixed protected installation.
 

The quality of material used for insulation and sheathing and high quality copper conductors make the cables both flexible, durable, resistant to torsion and to high temperatures. Nexans offers more than a decade of experience in the wind energy market. Our expertise makes WINDLINK® cables highly recommended for wind turbines.

 

Main characteristics

  • Frequent torsion: Excellent torsion behavior
  • Industrial cables resistant to high temperatures
  • Heavy duty
  • Temperature on core: 90°C in normal use; 250°C in short circuit
  • Water resistance: AD2, AD6
  • Corrosive and polluting substances resistance: AF3
  • Outdoor use : temporary and permanent
  • Impact resistance: AG2
  • Oil resistant ASTM/IRM 902 -
  • UV resistant for external application
  • Ozone resistant
  • Fire performances : Flame retardant (IEC/EN 60332-1, EN 50265-1 and 2-1)
    and Fire retardant (IEC/EN 60332-3 Cat C; EN 50266-1 and 50266-2-4)

 

Design 

1. Conductor :
Flexible (fine wire class 5 of IEC/EN 60228)
Annealed plain copper - Optional PET separator

2. Insulation :
Special cross-linked EI7 rubber for high temperatures 
Optional PET tape on insulation or assembling

3. Sheath:
High mechanical performance
Special cross-linked EM7 rubber 
Oil ,Ozone and flame  and  fire retardant.
Colour :black


 TOP
Characteristics
Construction characteristics
Conductor material Plain annealed copper  
Electrical characteristics
Rated Voltage Uo/U (Um) 450 / 750 V (600/1000)  
Mechanical characteristics
Torsion test max. +/- 4 turns for 10 meters max:150° per meter  
Mechanical resistance to impacts Good  
Usage characteristics
U.V resistance Very good  
Fire retardant IEC 60332-3 Cat.C  
Flame retardant EN 50265-1 & EN 50265-2-1 & IEC 60332-1  
Smoke density LSF EN 61034-2  
Oil resistance Good  
Watertightness AD2 to AD6  
Ambient dynamic operating temperature, range -40 .. 50°C  
Ambient static operating temperature, range -40 .. 50°C  
Operating temperature, range -40 .. 90°C  
Minimum operating temperature -40°C  
Max. conductor temperature in service 90°C  
Short-circuit max. conductor temperature 250°C  

 TOP
Complementary technical for Windlink®

Usage characteristics:

Mechanical stress :

(on the whole cable, per mm² of a cross section of plain copper core)

  • In normal use : 15 N/mm²

 

Mechanical characteristics:

Bending Radius

Mobile use = 6 x External diameter.
Static use = 3 x External diameter , if the external diameter < 12mm, 4 x if the external diameter >12 mm.

 

Electrical characteristics:

Permissible current rating: 

  • Permanent temperature of operation on the core 90°C
  • Ambient temperature for an outdoor installation  30°C

 

Correction factors according for other ambient temperature : according to IEC 60364.5.523 table 52.D1 or DIN VDE 0298-4 Table 15

Ambient
temperature (°C)
10 15 20 25 30 35 40 45 50 55 60 65 70 75
factors  1.17 1.13 1.09 1.04 1 0.96 0.91 0.87 0.82 0.76 0.69 0.62 0.54 0.45

The Voltage drop has been determined with Cos φ= 0.8

 

 Short circuit : constant K=139 Amps for 1 second, acc.to IEC 60949 ( short circuit temperature +250°C and conductor temperature +90°C)

 

 


 TOP
WINDLINK® H07ZZ-F

  

Other properties

 

Tests according to HD22.13
UV resistant sheath black sheath is UV resistant for external application
Oil resistant sheath good in oils, greases, gear box oil, etc
Ozone resistant sheath according to HDD 22-1
  • ASTM/IRM 902
24h at 100°C
  • Gear box oil as Tribol 1710/320 or equiv oil
72h at 40°C or 24h at 100°C
  • Hydraulic oil as Mobil DTE 13m or equiv oil.
72h at 40°C or 24h at 100°C

 


 TOP
Selling delivery information

Marking

WINDLINK® NEXANS 213 USE< HAR >H07ZZ-F -40 +90°C
Nb cores X (or G) S
X = without G/Y
G = with G/Y
S = cross section (mm2)
Week + year manufacturing
meter marking

 

Insulated Cores identification

• 1 core = Black (preferential)
• 2 cores = Brown + Blue
• 3 cores = Green/Yellow +Blue + Brown (G)
Brown + Black + Grey (X S>4mm²)
Blue + Brown + Black (X S 1.5 & 2.5 mm²)
• 4 cores = Green/Yellow + Brown + Black + Grey (G)
Blue + Brown + Black + Grey (X S 1.5 & 2.5 mm²)


Nexans © copyright 2001 - 2012   Legal Notice | Contact Us | Site Map